Home > Products > Gas Solenoid Valve > LCV-HPC series solenoid safety valve

  • High Pressure Fast Opening Solenoid Valve

    High Pressure Fast Opening Solenoid Valve

    Opening time <1 seconds

    Closing time <1 seconds

    Maximum operating frequency: 20 times per minute

    Maximum working pressure: 500 mbar 

    Equipped with G1/4 aperture bypass hole

    Built-in filter

    Protection level :IP54

    Sealing material: Nitrile Rubber


    Share
    INQUIRE NOW
LCV-HPC series solenoid safety valve
Description and Application

Product Details

High pressure gas solenoid valve can be widely used in gas safety transmission to provide gas supply for opening and closing or emergency cut off.

Can be applied to gas, such as natural gas, methane, and liquefied petroleum gas.

Under Pressure between 4-6Kg and below that, it can be automatically opened and closed, direct-acting fast-opening and fast-closing, and energy-saving design, the power consume while working is half of when it stars up, and the blue light is displayed after start up to achieve the working mode visualization.

Adopting a company’s patent, with several appearance and practical patents.

20180918164215.jpg






















20180918164211.jpg





















Operation and Installation 

Normally closed, fast open when the power is on; close immediately when the power is off.

There are bypass holes on both sides of the valve body, and its diameter is G1/4".

Technical Specification

Technical Parameters

Opening time <1 seconds

Closing time <1 seconds

Maximum operating frequency: 20 times per minute

Maximum working pressure: 500 mbar 

Equipped with G1/4 aperture bypass hole

Built-in filter

Protection level :IP54

Sealing material: Nitrile Rubber

Body material: Aluminum alloy for valve;

AISI 302 steel spring

Ambient temperature: -15 ° C - 60 ° C

Coil temperature: 65 ° C


Standards and certification

Achieving "A" standard

Meet EN161:2002 standard

Meet UK and European gas standards

CE certification 


Electrical specification

Rated voltage: 50/60Hz, 230Vac (and other specific) 

Coil grade F, can be 360°rotation, can work 100% continuously for a long time.


Overall Dimensions and item No.

TYPE

 

Passage

DN

Connection 

 

Max Pressure

Mbar

Operating temperature

Protection

 

LCV-HPC20

20

RP  3/4″

5000

-15 to 60

IP54

LCV-HPC25L

25

RP  1″

5000

-15 to 60

IP54

LCV-HPC325

25

RP  1″

5000

-15 to 60

IP54

LCV-HPC332L

32

RP  1¼″

5000

-15 to 60

IP54

LCV-HPC332

32

RP  1¼″

5000

-15 to 60

IP54

LCV-HPC40

40

RP  1½″

5000

-15 to 60

IP54

LCV-HPC50

50

RP  2″

5000

-15 to 60

IP54





Type

Length

L(mm)

Width

W(mm)

Height    

   H(mm)

Coil radius of gyration S(mm)

LCV-HPC20

100

70

153

56

LCV-HPC25L

100

70

153

56

LCV-HPC325

112

82

167

59

LCV-HPC332L

112

82

167

59

LCV-HPC332

150

104

208

68

LCV-HPC40

150

104

208

68

LCV-HPC50

150

104

208

68


Installation Dimension


1.png

Online Services
Whatsapp Skype